Georgetown University in Washington, DC is one of the world’s leading academic and research institutions, classified as a Very High Research Activity (RU/VH) University by The Carnegie Foundation for the Advancement of Teaching.
Completed in 2012, Regents Hall is a state-of-the art research and teaching center for biology, chemistry, and physics. With 154,000-square-feet of research space, it houses three classrooms, 12 teaching labs, and dozens of research labs in addition to conference rooms and student lounges. Knowing the enormous utility costs associated with running a science facility, Georgetown Energy and Utilities department invited Aircuity to evaluate how their platform could help reduce energy consumption while improving lab safety.
Aircuity assessed the labs on an individual basis and determined that 65 were a good fit for the application of demand-control ventilation. A proposal with a calculated annual savings was presented to GU management and the project soon got underway. The system installation took three months with very minimal impact to research and teaching activities. Subsequently, the new control system was commissioned in May 2017. Within the first year, the actual energy savings was nearly $124,000.
Soon after completion, Georgetown’s analytics identified 5 areas of opportunity that the university could address to reach their full savings potential.
Fume Hood Behavior:
Data from the Aircuity system showed that ten fume hoods were left at full operational height continuously for several weeks. With each hood averaging ~$4,500/year to operate (roughly same utility cost as a house), the ability to easily identify issues and modify behavior relative to these hoods provides for significant savings. Had these 10 hoods remained fully opened for year it would have cost the university $45,000.
Using this information, Environmental and Occupational Safety Manager, Casey Cahill, worked with Science Building Manager, Kavita Tanksale, researchers and students, to ensure these sashes are closed when the fume hoods are not in use.This action has achieved a measurable improvement.
Rooms with High Thermal Loads:
There were 13 rooms with cfm higher than their targeted rate. These excess flows total 2745 cfm, or approximately $13,725 in missed ene
Rooms with Frequent DCV Responsesoms with Frequent DCV Responses
These events are all within normal operating parameters and are sufficiently ventilated by the system.They caused an excess flow of approximately 750 cfm.
Incorrectly Programmed Fumehoods
Fume hoods were found going to their max based on occupancy, not sash position.Adding up the combined CFM that these hoods are running over their minimum, during the occupied periods (approximately 8:00 am to 8:00 pm), the difference between the min and max flows is a combined 7500 CFM.We see this issue during 60 of the 168 hours in a week = 35.7% of the time.
Estimating that a researcher works in their fume hood about 10% of the time,there is opportunity for saving 6750 CFM.
Increased Fan Power for More Duct Static in One Room
Aircuity’s lab ventilation energy model was run with an increase static of 20% at the exhaust fans only (1.5 to 1.8 = 20%).There was about 70,000 kWh attributed to the increase.
In addition to understand the full savings opportunity, Georgetown’s Environmental, Health & Safety department used the information displayed at the Aircuity portal to verify the high performance of rooms, relative to Indoor Environmental Quality (IEQ). The MyAircuity web app automatically ranks the rooms by their IEQ performance. Casey Cahill looked at the analytics and immediately identified a room that had considerably more IEQ events over the prior two weeks. Armed with this information he went to the specific room to contain the source of the contaminants.
Using the Aircuity 2.0 Platform, Georgetown University has:
• Delivered energy savings in an already cutting-edge building
• Gained quick and easy access to actionable information that is valued by multiple stakeholders
• Created measurably better environments for all occupants
Currently, Georgetown is developing a second project for its main campus.
ABOUT AIRCUITY
Aircuity creates smart airside solutions through its intelligent building platform, significantly reducing energy costs and improving the indoor environmental quality for occupants. As the demand control solution, Aircuity optimizes ventilation rates through its patented technology. As a result, commercial, institutional and lab building owners can lower operating costs, protect occupants and verifiably reduce energy use by as much as 60 percent. Founded in 2000 and headquartered in Newton, MA, Aircuity’s solutions have benefited over 400 organizations such as Google, Amazon, Eli Lilly, Masdar City, the University of Pennsylvania, and the University of California-Irvine. For additional information on the company and its solutions, please visit: www.aircuity.com.